E10SMEW6 Pitched Roof Eaves Insulation at Ceiling level

Build Up

Solid External Masonry Wall

215mm Aircrete Solid Wall (λ = 0.19 W/mK)

Render & Insulation (λ = 0.038 W/mK)

Pitched Roof Eaves (minimum pitch 40°)

400mm insulation quilt (0.044W/mK) at Ceiling Level

 

This LABC Registered Construction Detail is only valid for use with building work intended to follow the guidance in the following:

England

  • Approved Document L1A and L2A (2013 edition incorporating amendments up to and including 2016)
  • Approved Document L1B (2010 edition incorporating amendments up to and including 2018)
  • Approved Document L2B (2010 edition incorporating amendments up to and including 2016)

NOTE: This LABC Registered Construction Detail should not be used for Approved Document L Volume 1 and 2 (2021 edition) or any subsequent amendments.

Wales

  • Approved Document L1A, L1B, L2A and L2B (2014 edition incorporating amendments up to and including 2016)

NOTE: This LABC Registered Construction Detail should not be used for Approved Document L Volume 1 and 2 (2022 edition) or any subsequent amendments.

 

Architect downloads

Registered Detail certificates