Where to install smoke alarms and heat alarms

07.03.2018
Blog Post
Match and smoke - fire alarms and heat alarms

Smoke alarms have been a standard feature in new homes since they were first introduced into Approved Document B in 1992. Whilst they are now installed as a matter of course, just how much consideration is given to ensuring that they are located correctly?

Siting alarms correctly throughout a property is vital to ensure they provide lifesaving detection and respond as quickly as possible in the event of a fire. Every property is different, but here are some basic rules to follow.

Placing of smoke alarms and heat alarms

  • Alarms should be sited on the ceiling, as centrally as possible within the room/area they are installedSmoke alarms and heat alarms - where to place
  • Site 300mm away from walls and light fittings – this is to ensure that they are away from any ‘dead air’ spaces that occur in corners and spaces where the airflow may be blocked
  • There should be an alarm within 3m of every bedroom door to ensure audibility
  • There should be an alarm within 7.5m of every habitable room
  • Alarms should be positioned between high risk rooms and bedrooms
  • Alarms should not be sited within bathrooms or too close to a bathroom door as steam/moisture can affect them
  • Ceiling-mounted detectors should be located such that their sensitive elements are between 25mm and 150mm below the ceiling in the case of heat detectors, or between 25mm and 600mm below the ceiling in the case of smoke detectors
  • Be fixed where they can be reached to maintain, therefore not over the stairs
  • Not placed above heaters or air conditioning units/vents
  • Where the stairs are open to the rooms at ground floor including the kitchen a heat detector is required in the kitchen

Other factors to consider

  • On stairways site alarms on the flat ceilings between the rooms and stairs at each level – do not site on the sloped ceiling directly above the stairs
  • Peaked and sloped ceilings – for smoke alarms site a maximum of 600mm vertically down from the apex, for heat alarms a maximum of 150mm vertically down from the apex
  • Beams (where the depth of the beam is less than 10% of the room height) – site the alarm twice the depth of the beam or 500mm away from the beam, whichever is less
  • Beams (where the depth of the beam is more than 10% of the room height) – treat the beam as a wall and fit alarms on both sides of the beam, or if the beam is less than 600mm deep site an alarm on the underside of the beam

NB Click the image above to download a bigger version.

Further information

The dos and don'ts of mains powered smoke alarms and battery alarms

 

Please Note: Every care was taken to ensure the information was correct at the time of publication. Any written guidance provided does not replace the user’s professional judgement. It is the responsibility of the dutyholder or person carrying out the work to ensure compliance with relevant building regulations or applicable technical standards.


This article was updated on 22 March 2022

Comments

Interlinked Fire alarm

Submitted 3 months 1 week ago

I have gone through all of the steps but pairing the remote to the others does not work. Can I re do the process.

LABC response

Submitted 3 months 1 week ago

Hi,

Thank you for your enquiry. LABC is a membership organisation, providing advice and support to its member local authorities around England and Wales. As a result, LABC cannot comment on the performance and criteria for products or give any advice on their operation.

Please contact the product manufacturer for further guidance.

Best,
LABC team.


Personal or identifiable details have been removed from the above message.

fire alarms

Submitted 2 months 1 week ago

LABC says smoke alarms are required 3 m from bedrooms and 7.5 m from habitable rooms where do you get that from? Is it in the building regulations or the approved documents or is it a BS number? many thanks for considering my question.

LABC response

Submitted 2 months ago

Hi,

Thank you for your recent question. The guidance in relation to the siting of LD3 smoke alarms is contained in section 11 of BS 5839-6: 2019.

Best,
LABC team

Add new comment

This question is for testing whether or not you are a human visitor and to prevent automated spam submissions.

Sign up to the building bulletin newsletter

Over 48,000 construction professionals have already signed up for the LABC Building Bulletin.

Join them and receive useful tips, practical technical information and industry news by email once every 6 weeks.

Subscribe to the Building Bulletin