Where to install smoke alarms and heat alarms

Blog Post
Match and smoke - fire alarms and heat alarms

Smoke alarms have been a standard feature in new homes since they were first introduced into Approved Document B in 1992. Whilst they are now installed as a matter of course, just how much consideration is given to ensuring that they are located correctly?

Siting alarms correctly throughout a property is vital to ensure they provide lifesaving detection and respond as quickly as possible in the event of a fire. Every property is different, but here are some basic rules to follow.

Placing of smoke alarms and heat alarms

  • Alarms should be sited on the ceiling, as centrally as possible within the room/area they are installedSmoke alarms and heat alarms - where to place
  • Site 300mm away from walls and light fittings – this is to ensure that they are away from any ‘dead air’ spaces that occur in corners and spaces where the airflow may be blocked
  • There should be an alarm within 3m of every bedroom door to ensure audibility
  • There should be an alarm within 7.5m of every habitable room
  • Alarms should be positioned between high risk rooms and bedrooms
  • Alarms should not be sited within bathrooms or too close to a bathroom door as steam/moisture can affect them
  • Ceiling-mounted detectors should be located such that their sensitive elements are between 25mm and 150mm below the ceiling in the case of heat detectors, or between 25mm and 600mm below the ceiling in the case of smoke detectors
  • Be fixed where they can be reached to maintain, therefore not over the stairs
  • Not placed above heaters or air conditioning units/vents
  • Where the stairs are open to the rooms at ground floor including the kitchen a heat detector is required in the kitchen

Other factors to consider

  • On stairways site alarms on the flat ceilings between the rooms and stairs at each level – do not site on the sloped ceiling directly above the stairs
  • Peaked and sloped ceilings – for smoke alarms site a maximum of 600mm vertically down from the apex, for heat alarms a maximum of 150mm vertically down from the apex
  • Beams (where the depth of the beam is less than 10% of the room height) – site the alarm twice the depth of the beam or 500mm away from the beam, whichever is less
  • Beams (where the depth of the beam is more than 10% of the room height) – treat the beam as a wall and fit alarms on both sides of the beam, or if the beam is less than 600mm deep site an alarm on the underside of the beam

NB Click the image above to download a bigger version.

Further information

The dos and don'ts of mains powered smoke alarms and battery alarms

 

Please Note: Every care was taken to ensure the information was correct at the time of publication. Any written guidance provided does not replace the user’s professional judgement. It is the responsibility of the dutyholder or person carrying out the work to ensure compliance with relevant building regulations or applicable technical standards.


This article was updated on 22 March 2022

Comments

Smoke alarm panel positioning

Submitted 4 months 4 weeks ago

We’re having a smoke alarm installed and would like to know if the panel can be positioned a few metres away from the front door as the building is grade 2 listed and it would harm the character of the building if right by the front door? The panel would still be visible upon entry where we’d like it - just not in your face as it would be if by the front door. Thanks

LABC Response

Submitted 3 months 3 weeks ago

Thank you for your enquiry.

The fire alarm panel would need to be in an agreed location, this would need to be assessed in your application to the Local Authority for Building Regulations in consultation with the Local Fire and Rescue Service who would consider the Listed Building status. Therefore, we would advise that you contact your Local Authority.

Best,
LABC Team

Heat alarm installation

Submitted 2 months 3 weeks ago

Hi, we had a 2-storey extension built and someone mentioned we need to install a heat alarm. The Building Regs say a heat alarm only needs to be placed in the kitchen where it is NOT separated by a door. Our kitchen is separated by a door to the rest of the house. Hence why we didn’t bother. We have interlinked smoke detectors, one mains-powered.

Do we still need one?

And if so, do we need one elsewhere? And if so, where do they need to be placed and which ones can be battery-powered, which ones mains-powered?

The information is so confusing.

Many thanks!

LABC Response

Submitted 2 months 3 weeks ago

Hi,

Thank you for your enquiry, however, the answer will be dependent upon your particular circumstances, and this is not something that LABC can help with.

Please discuss the details of your proposals with your professional advisors and contact the Building Control team at your Local Authority to discuss project specific requirements.

Best,
LABC Team

Heat alarms

Submitted 1 month 2 weeks ago

OK thanks. Which document should I be looking at for heat alarm requirements (for a private residential house)? The work was done in 2017.

LABC Response

Submitted 3 weeks 6 days ago

Guidance for fire detection and alarm systems, including heat alarms can be found in section 1 of Approved Document B (fire safety) volume 1: Dwellings, 2019 edition incorporating 2020 and 2022 amendments is the current edition, albeit they may be updated by Central Government.

Best,
LABC Team

Add new comment

CAPTCHA
This question is for testing whether or not you are a human visitor and to prevent automated spam submissions.

Sign up to the building bulletin newsletter

Over 48,000 construction professionals have already signed up for the LABC Building Bulletin.

Join them and receive useful tips, practical technical information and industry news by email once every 6 weeks.

Subscribe to the Building Bulletin